Transformer Percent Impedance: %Z
Transformer percent impedance is a measured value stamped on the nameplate and is actually a voltage measurement. It's a tested value that the manufacturers do for power distribution transformers and is used in the fault current calculation. This is important for coordinating over-current protection devices (OCPD), short circuit analysis, harmonic analysis and arc flash studies.
The percent impedance is the percent of the rated voltage required to cause the rated current to flow when the secondary windings are short-circuited at the rated voltage tap and frequency.
Example of Percent Impedance
If a transformer has a 6.33% impedance, it would require 6.33% of the input primary voltage to cause 100% of the rated current on the secondary windings when a worst case fault occurs. In electrical distribution systems, the worst case fault is when a low impedance metal bar shorts the lines and is called a bolted fault.
Now if 100% of the voltage is applied to the primary input, then approximately 100/6.33 = 15.8x rated current would flow in the secondary winding under a worse case fault. This is the maximum short circuit current that we would have in your system.
Percent Impedance Testing
The worst case fault condition is tested with the secondary leads of a transformer bolted together, actually bolted with copper bars with an ammeter placed in series.
Very carefully, the voltage on the primary lines is stepped up until the secondary full load current is reached.
For example, this 2500 kVA, 12.47 kV to 600/347 V transformer shown in the photo:

Once the secondary current reaches 2406A, a voltage reading is taken on the primary to see what input voltage is required to reach this full load current rating on the secondary. In this case, the technician would read 789.35 V.
Doing a simple calculation:

Important note to electrical engineers:
Always read the measured % Impedance from the nameplate, not the data sheet. On this transformer in Edmonton, Alberta, the nameplate read 6.33 while the accompanying literature stated only 6%. It was a small difference but accuracy is important on electrical assessments.
Typical Percent Impedance Values
As electrical consulting engineers, these are the typical impedance levels we've seen on transformers.
Transformer Size (kVA) |
Typical %Z Values |
---|---|
0-150 | Below 4% |
151-300 | 4% |
301-600 | 5% |
601-2500 | 6% |
2501-5000 | 6.5% |
5001-7500 | 7.5% |
7501-10000 | 8.5% |
Above 10kVA | 9.5% |
The simple non-destructive percent impedance test on a transformer gives an accurate reading for fault calculations.